TABLE 8—702B WITH ICM FIOP ELECTRICAL DATA

UNIT

SIZE 702B

V-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR

FAN

MOTOR

INDOOR

FAN

MOTOR

ELECTRIC

HEAT

SINGLE POINT

POWER SUPPLY

MIN MAX

RLA

LRA

FLA

FLA

Nominal kW*

FLA

MCA

MAX FUSE

OR CKT. BKR.

MOCP

024

208/230–1–60 187

253

13.5

61.0

0.9

4.3

-/-

3.8/5.0
5.4/7.2

7.5/10.0

-/-

18.1/20.8
25.9/30.0
36.1/41.7

22.1/22.1
27.9/31.4
37.8/42.9
50.5/57.5

30/30
30/35
40/50
60/60




030

208/230–1–60 187

253

14.7

73.0

0.9

4.3

-/-

3.8/5.0
5.4/7.2

7.5/10.0

-/-

18.1/20.8
25.9/30.0
36.1/41.7

23.5/23.5
27.9/31.4
37.8/42.9
50.5/57.5

30/30
30/35
40/50
60/60




036

208/230–1–60 187

253

15.4

83.0

0.9

6.8

-/-

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0

-/-

18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5

27.0/27.0
31.1/34.5
40.9/46.0
53.6/60.6
76.2/86.6

35/35
35/40
50/50

60/–



–/70

80/90

042

208/230–1–60 187

253

18.6

105.0

0.9

6.8

-/-

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0
15.0/20.0

-/-

18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3

31.0/31.0
31.1/34.5
40.9/46.0
53.6/60.6
76.2/86.6

98.8/112.7

40/10
40/40
50/50

60/–




–/70

90/90

100/125

048

208/230–1–60 187

253

20.5

109.0

1.6

6.8

-/-

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0
15.0/20.0

-/-

18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3

34.0/34.0
34.0/34.5
40.9/46.0
53.6/60.6
76.2/86.6

98.8/112.7

40/40
40/40
50/50

60/-




–/70

90/90

100/125

060

208/230–1–60 187

253

27.6

158.0

1.6

9.1

-/-

3.8/5.0
5.4/7.2

7.5/10.0

11.3/15.0
15.0/20.0

-/-

18.1/20.8
25.9/30.0
36.1/41.7
54.2/62.5
72.2/83.3

45.2/45.2
45.2/45.2
43.8/48.9
56.5/63.5
79.1/89.5

101.6/115.5

60/60
60/60
50/50

60/-




–/70

90/90

110/125

* Heater capacity (kW) based on heater voltage of 208-v & 240-v. If power distribution voltage to unit varies from rated heater voltage, heater kW will vary accordingly. Refer
to

Multiplication Factors

Table 23.

—19—