Bryant 683B User Manual

Page 16

Advertising
background image

TABLE 5—ICM FIOP PHYSICAL DATA—UNIT 683B (CONTINUED)

THIS DATA APPLIES TO 683B UNITS WITH THE ICM INDOOR MOTOR FIOP

UNIT SIZE 683B

048090

048115

048130

060090

060115

060130

NOMINAL CAPACITY (ton)

4

4

4

5

5

5

OPERATING WEIGHT (lb.)

409

409

409

504

504

504

COMPRESSORS

Quantity

Scroll

1

REFRIGERANT (R-410A)

Quantity (lb.)

10.6

10.6

10.6

12.4

12.4

12.4

REFRIGERANT METERING DEVICE

Orifice Indoor (in.)

Check-Flo-Rater™ Piston

.076

.076

.076

.088

.088

.088

REFRIGERANT METERING DEVICE

Orifice Outdoor (in.)

Check-Flo-Rater™ Piston

0.046 (2)

0.046 (2)

0.046 (2)

0.052 (2)

0.052 (2)

0.052 (2)

OUTDOOR COIL

Rows...Fins/in.

Face Area (sq ft)

2...17

13.5

2...17

13.5

2...17

13.5

2...17

15.4

2...17

15.4

2...17

15.4

OUTDOOR FAN

Nominal Cfm

Diameter (in.)

Motor Hp (Rpm)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

INDOOR COIL

Rows...Fins/in.

Face Area (sq ft)

4...15

4.7

4...15

4.7

4...15

4.7

4...15

5.7

4...15

5.7

4...15

5.7

INDOOR BLOWER

Nominal Airflow (Cfm)

Size (in.)

Motor (HP)

1600

11 X 10

3/4

1600

11 X 10

3/4

1600

11 X 10

3/4

1750

11 X 10

1.0

1750

11 X 10

1.0

1750

11 X 10

1.0

FURNACE SECTION*

Burner Orifice No. (Qty...Drill Size)

Natural Gas

Burner Orifice No. (Qty...Drill Size)

Propane Gas

3...38
3...46

3...33
3...42

3...31
3...41

3...38
3...46

3...33
3...42

3...31
3...41

HIGH-PRESSURE SWITCH (psig)

Cutout

Reset (Auto)

610 ± 15
420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

Reset (Auto)

20 ± 5

45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

TABLE 6—683B WITH ICM FIOP ELECTRICAL DATA

UNIT

SIZE 683B

V-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR FAN

MOTOR

INDOOR FAN

MOTOR

POWER SUPPLY

MIN

MAX

RLA

LRA

FLA

FLA

MCA

MAX FUSE

OR CKT. BKR.

024

208/230–1–60

187

253

13.5

61.0

0.9

4.3

22.1

30

030

208/230–1–60

187

253

15.9

73.0

0.9

4.3

25.1

35

036

208/230–1–60

187

253

16.9

83.0

1.6

6.8

29.5

40

042

208/230–1–60

187

253

22.4

105.0

0.9

6.8

35.7

50

048

208/230–1–60

187

253

21.3

109.0

1.6

6.8

35.0

50

060

208/230–1–60

187

253

27.6

158.0

1.6

9.2

45.3

60

—16—