f. Loosen set-screw that secures wheel to motor shaft,

remove screws that secure motor mount brackets to
blower housing, and slide motor and motor mount out of
blower housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or cleaning

blower wheel, be sure not to disturb balance weights
(clips) on blower wheel vanes.

c. Remove caked-on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from wheel
and housing with vacuum cleaner, using soft brush
attachment. Remove grease and oil with mild solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure set-screw(s) are

tightened on motor shaft flats and not on round part of
shaft.

f. Pivot blower access panel back into place. Adjust wire

assemblies so that wiring follows proper pathways.

g. Reinstall unit access panel.

3. Restore electrical power, then gas supply to unit. Start unit

and check for proper blower rotation and motor speeds
during heating and cooling cycles.

TROUBLESHOOTING

START-UP CHECKLIST

TABLE 2—ICM FIOP PHYSICAL DATA—UNIT 583B (CONTINUED)

THIS DATA APPLIES TO 583B UNITS WITH THE ICM INDOOR MOTOR FIOP

UNIT SIZE 583B

048090

048115

048130

060090

060115

060130

NOMINAL CAPACITY (ton)

4

4

4

5

5

5

OPERATING WEIGHT (lb.)

421

421

421

468

468

468

COMPRESSORS

Quantity

Scroll

1

REFRIGERANT (R-410A)

Quantity (lb.)

9.5

9.5

9.5

10.0

10.0

10.0

REFRIGERANT METERING DEVICE

Orifice ID (in.)

Check-Flo-Rater™ Piston

.073

.073

.073

.086

.086

.086

CONDENSER COIL

Rows...Fins/in.

Face Area (sq ft)

2...17

12.3

2...17

12.3

2...17

12.3

2...17

16.4

2...17

16.4

2...17

16.4

CONDENSER FAN

Nominal Cfm

Diameter (in.)

Motor Hp (Rpm)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

3300

22

1/4 (1100)

EVAPORATOR COIL

Rows...Fins/in.

Face Area (sq ft)

4...15

4.7

4...15

4.7

4...15

4.7

4...15

4.7

4...15

4.7

4...15

4.7

EVAPORATOR BLOWER

Nominal Airflow (Cfm)

Size (in.)

Motor (HP)

1600

11 X 10

3/4

1600

11 X 10

3/4

1600

11 X 10

3/4

2000

11 X 10

1.0

2000

11 X 10

1.0

2000

11 X 10

1.0

FURNACE SECTION*

Burner Orifice No. (Qty...Drill Size)

Natural Gas

Burner Orifice No. (Qty...Drill Size)

Propane Gas

3...38
3...46

3...33
3...42

3...31
3...41

3...38
3...46

3...33
3...42

3...31
3...41

HIGH-PRESSURE SWITCH (psig)

Cutout

Reset (Auto)

610 ± 15
420 ± 25

LOSS-OF-CHARGE/LOW-PRESSURE SWITCH

(Liquid Line) (psig)

Cutout

Reset (Auto)

20 ± 5

45 ± 10

RETURN-AIR FILTERS (in.)

Throwaway

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

24 X 30 X 1

* Based on altitude of 0 to 2000 ft.

TABLE 3—583B WITH ICM FIOP ELECTRICAL DATA

UNIT

SIZE 583B

V-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

OUTDOOR FAN

MOTOR

INDOOR FAN

MOTOR

POWER SUPPLY

MIN

MAX

RLA

LRA

FLA

FLA

MCA

MAX FUSE

OR CKT. BKR.

024

208/230–1–60

187

253

13.5

61.0

0.9

4.3

22.1

30

030

208/230–1–60

187

253

14.7

73.0

0.9

4.3

23.6

30

036

208/230–1–60

187

253

15.4

83.0

0.9

6.8

27.0

35

042

208/230–1–60

187

253

18.6

105.0

0.9

6.8

31.0

40

048

208/230–1–60

187

253

20.5

109.0

1.6

6.8

34.0

40

060

208/230–1–60

187

253

27.6

158.0

1.6

9.2

45.2

60