L.B. White FA-MCS User Manual

Page 12

Advertising
background image

Press the center soft key EDIT.

Press the up/down keys to enable (ENA) or disabled (dSA)

Zone 1 Temperature Sensor 1. See Fig. 26. Make the
same selections for sensors 2 through 4 for Zone 1.

FIG. 26

Once all have been selected for Zone 1, Temperature
Sensor 1 and 2, press the right soft key NEXT to
access Zone 2. Repeat the same procedure for Zone 2.
When completed, press the left soft key DONE.

To continue set-up, press right soft key NEXT. The following
screen is displayed.

CALIBRATING TEMPERATURE SENSORS

This selection allows correlation between the room
controller’s sensors and the SmartBox

sensors.

FIG. 27

Press the center soft key EDIT. The following screen is

displayed.

FIG. 28

-- Before making any adjustments, you must allow the

temperature between the room controller sensors
and the SmartBox

sensors to stabilize.

-- Once temperatures have stabilized, use the up/down

keys to enter room temperature sensor offset.

Press the right soft key NEXT to set temperature offset for

Zone 1, Temperature Sensors 1 and 2. Complete the same
process for Zone 2, Temperature Sensor 1 and 2. Use the
up/down keys accordingly.

-- Example: If the room controller reads 70 F and the

SmartBox

reads 69 F, set the offset temperature 1F

by pressing the up key.

Press the leftsoft key DONE, then press NEXT. The

following screen is displayed

FIG. 29

Press the center soft key EDIT to view the heat load

percent in Zone 1. See Fig. 30. To view Zone 2, press right
center soft key NEXT

FIG. 30

Press the up/down keys and center soft key

simultaneously to exit the set-up mode and to return you
back to the Home Screen. Now determine your
temperature curve.

12