Testing the manual reset high limit switches, Burner orifice and gas control valve – L.B. White 350 Premier Dual Fuel User Manual

Page 19

Advertising
background image

This heater has two limit switches. One is located at the

burner end of the heater. The other is located on the fan

housing at the motor end of the heater. Both high limit

switches should be tested a minimum of once per year

when the heater is given a thorough cleaning.

1. Remove the high limit switches.

2. Holding the switch by one of its mounting legs, apply

a small flame only to the sensing portion on the back

of the switch. Be ccareful nnot tto m

melt tthe pplastic

housing oof tthe sswitch w

when cconducting tthis ttest.

3. Within a minute, you should hear a pop coming from

the switch, which indicates the contacts of the switch

have opened.

4. Allow the switch to cool for about a minute before

firmly pressing its reset button. The switch may have

a red cap over the button. If you removed the cap to

reset the switch, ensure you put it back on.

5. Check for electrical continuity across the switch

terminals to make sure the contacts have closed.

FIG. 23

RESET BUTTON

SENSING
SURFACE

TERMINAL

FLAME

MOUNTING
LEG

1. Remove hose and pipe nipple from control valve inlet.

2. Open burner end door.

3. Remove screws from gas control bracket and

disconnect control valve’s electrical wiring. See Fig.

24.

FIG. 24

4. Remove burner panel. See Fig. 25.

FIG. 25

5. Remove burner retaining bolt from under base at gas

control end of heater. See Fig. 26.

FIG. 26

6. Lift and pivot the gas train assembly so orifice is

exposed. See Fig. 27. Remove control valve or orifice

as needed.

FIG. 27

SCREW

BOLT

TESTING THE MANUAL RESET HIGH LIMIT SWITCHES

WARNING

Fire H

Hazard

Do not operate the heater with the high limit switch

bypassed.

Operating the heater bypassed high limit switch may

lead to overheating, possibly resulting in a fire, with

subsequent damage to the heater or property damage.

ORIFICE

19

BURNER ORIFICE AND GAS CONTROL VALVE