Gas pressure checks – L.B. White 350 Premier Dual Fuel User Manual

Page 21

Advertising
background image

ATTENTION

The following explains a typical procedure to be followed

in checking gas pressures.

The gas pressures will vary depending upon fuel type.

Consult the dataplate on the heater or page 4 in this

manual for specific pressures to be used in conjunction

with this procedure.

Gas pressure measured at the inlet to the gas valve is

Inlet Pressure and gas pressure measured at the outlet

of the gas valve is Burner Manifold Pressure.

MATERIALS REQUIRED

Quantity

Description

2

Gas pressure gauges capable of reading

up to 35 in. W.C. (may also be ordered

from L.B. White, part number 00764)

A. PPreparation

1. Disconnect the heater from the electrical supply and

close the fuel supply valve to the heater.

2. Open the case access panel at burner end of heater.

3. Brush or blow off any dust or dirt in the vicinity of the

gas control valve.

B. G

Gauge IInstallation

1. Locate the gas control pressure taps, see Fig. 31.

Remove the pressure tap plugs using a 3/16 in. allen

key.

2. Securely connect pressure gauges at these points.

3. Open the fuel supply valves to the heater and

reconnect the heater electrical supply.

4. Start the heater

C. R

Reading PPressures

1. With the heater operating, the pressure gauges

should read the pressures specified on the dataplate.

2. Do the readings at the inlet and outlet pressure

gauges agree with that specified on the dataplate?

If so, then no further checking or adjustment is

required. Proceed to section D.

3. If the inlet pressures do not agree with that specified

on the dataplate, then the regulator controlling gas

pressure to the heater requires adjustment.

4. If the inlet pressure is correct but the burner manifold

pressure does not agree with that specified on the

dataplate, then the gas control valve’s internal

pressure regulator needs adjsutment:

-- Remove the regulator cap on the control valve.

-- Using a standard screwdriver turn the adjusting

screw clockwise (to increase pressure) or counter-

clockwise (to decrease pressure) until the burner

manifold pressure is set.

-- Install regulator cap.

D. C

Completion

1. Once the proper inlet and burner manifold pressures

have been confirmed and/or properly set, close the

fuel supply valve to the heater and allow the heater to

burn off any gas remaining in the gas supply line.

2. Disconnect the heater from its electrical supply and

close fuel supply valve.

3. Remove the gauges.

4. Install pressure tap plugs.

5. Open fuel supply valve and reconnect electrical

supply to heater. Start the heater and check for gas

leaks.

6. Set thermostat to desired temperature.

FIG. 31

Gas Pressure Checks

WARNING

Do not disassemble the gas control valve.

Do not attempt to replace any components of the gas

control valve.

The gas control valve must be replaced if any physical

damage occurs to the control valve assembly.

Failure to follow this warning will result in fire or

explosions, leading to injury or death to humans, and

property damage.