5

GeniSys Control 24V Control Installation and Operation Manual

If the burner or control fails any of the

following tests, recheck control wiring. If the

burner or control still fails any tests, replace

the control.

Starting the System

Open the shut-off valve(s), if

applicable, in the supply line from

the oil tank.

Close the disconnect switch to

supply power to the burner.

Adjust the thermostat to call for heat.

If the pump has not been primed,

refer to “Priming the Pump” in this

manual.

Monitor burner operation to insure

that the burner ignites.

1.

2.

3.

4.

Wiring:

Incorrect Wiring Will

Result in Improper

Control Operation

GeniSys 24V wiring label colors may

not match the wire colors of the burner

or other manufacturers’ controls.
The GeniSys 24V Control should be

wired according to the equipment

manufacturer’s instructions.

y

y

CAUTION

Startup / Checkout

End the call for heat. Verify that the

burner turns off before leaving the

installation site.

Check Safety Features

Safe Start Check

Place a jumper across the cad

cell terminals.

Refer to the steps for

Starting the System” and

have the system call for heat.

Burner must not start. Verify that

the control remains in Standby

mode.

End the call for heat and remove

the cad cell jumper.

Simulate Flame Failure and Ignition

Failure

Refer to the steps for “Starting the

System” and have the system call

for heat.

After fl ame is established and the

burner igniter turns off (if wired for

interrupted ignition), simulate fl ame

failure by pulling the cord set out of

the solenoid valve.

At fl ame loss, the control will enter

Relight mode. The control will

immediately turn the igniter on.

After the 15 second lockout time,

the control will lock out the burner.

Verify that the burner motor and

igniter are off and that the burner

oil solenoid valve (if used) is not

energized.

Push the cord set back in.

To reset the control from lockout,

turn off power to the control for at

least 2 seconds.

Turn power on and verify that the

burner lights.

End the call for heat.

Insure that all control wiring is correct

prior to securing the control. Consult

equipment manual for details.

5.

1.

2.

3.

4.

1.

2.

3.

4.

5.

6.

7.

8.

Make sure all equipment wiring

complies with all local codes and

ordinances.

Make connections to the control’s

terminals as shown in Figure 2. Refer

to the label on the underside of the

control for wiring details.

Motor-off delay on a 7559P will be

disabled if the safety and operating

limits as shown in Figure 2 interrupt

power to the control’s red +24 volt wire.

Input power to the control’s red +24

volt wire must be provided from a fused

service switch, rated at 50 amps or less.