Sequence of Operation

Burner States

Standby: The burner is idle, waiting

for a call for heat.

Valve-On Delay: The igniter and

motor are on while the control delays

turning on the oil solenoid valve for

the programmed time.

Trial For Ignition: The oil solenoid

valve is energized. A fl ame should be

established within the factory set trial

for ignition time (“lockout time”).

4. Lockout: The control has shut

down for one of the following safety

reasons:

a. The trial for ignition (lockout)

time expired without fl ame being

established.

b. The cad cell detected fl ame at the

end of the Valve On Delay state.

c. The pre-set time allotment for

relighting is exceeded.

d. Failed welded relay check.

If the control detects a welded motor

contact, the motor only will cycle 5

1.

2.

3.

seconds on, 5 seconds off, 3 times

before locking out.

To reset the control from lockout

interrupt power for at least 2 seconds.

Ignition Carryover: Once fl ame is

established, the igniter remains on for

10 additional seconds to ensure fl ame

stability.

Run: The fl ame is sustained until the

call for heat is satisfi ed. The control

then switches to Motor-Off Delay,

if applicable, or it shuts down and

returns to Standby.

Relight: If the fl ame is lost while

the burner is fi ring, the control

immediately repeats the ignition

sequence. The control will continue

to Relight each time the fl ame is

lost, until it reaches a pre-set time

allotment. The control will then

go into Lockout instead of Relight.

This feature prevents excessive

accumulation of oil in the equipment’s

combustion chamber.

Motor-Off Delay: If applicable, the oil

solenoid valve is turned off and the

control delays turning the motor off for

the set motor-off delay time before the

control returns to standby. Note that to

utilize the motor off delay, power must

remain to the red wire after the call for

heat ends. (Enable input turned off,

see Figure 2.)

5.

6.

7.

8.

2

1

3

5

6

8

4

7

Standby

Motor-off

delay

Valve-on

delay

Trial for

ignition

Ignition

carryover

Run

Lockout

Relight

Reset and Service by Qualifi ed

Technician only.

Fire Hazard

WARNING