GeniSys Control 24V Control Installation and Operation Manual

Priming the Pump

To reset, interrupt power for at least 2

seconds.

Always verify the control functions

according to all specifi cations before

leaving the installation site.

Replace the control if it does not

operate as specifi ed.

1.

2.

3.

Prepare the burner for priming by
attaching a clear plastic hose over
the bleed port fi tting and fully opening
the pump bleed port. Use a suitable
container to collect purged oil.

Initiate a call for heat.

Bleed the pump until all froth and bubbles
are purged. If desired, terminate the call
for heat to return to Standby.

If prime is not established during the
valve on delay and the trial for ignition
times, repeat Step 3 until the pump is
fully primed and the oil is free of bubbles.

Terminate the call for heat, and the
control will resume normal operation.

Resetting From Lockout

1.

2.

3.

4.

5.

Do not allow oil to spray into a hot
combustion chamber while bleeding air
from the pump.
Install a gauge in the nozzle discharge
port tubing or fully open the pump
bleed valve to prevent oil spray from
accumulating in the combustion
chamber during the air bleed procedure.
Insure that all bubbles and froth are
purged from the oil supply system
before tightening the pump bleed valve.
Insure that the equipment is free of oil
and oil vapor before starting or resetting
the burner.

y

y

y

y

Failure to bleed the pump properly could

result in unstable combustion, hot gas

puff-back and heavy smoke.

Hot Gas Puff-Back &

Heavy Smoke Hazard

WARNING

Before starting or resetting

the control from lockout state,

troubleshoot the heating

system for the root cause(s) of

the lockout.

Fire & Smoke

Hazard

Make necessary repairs or adjustment

to ensure a safe start condition.
Insure that the equipment is free of

oil and oil vapors before starting or

resetting the burner.

y

y

WARNING

Maintenance

Oil heating systems require annual service

performed by a qualifi ed, professional

service agency. The 7559 primary control

should be inspected during this service

routine according to the following checklist:

The 7559 control has no

serviceable internal parts.

NOTICE

Inspect the exterior of the control.

Replace the control if there is any sign

of impact damage.
Use a multimeter to test the input

voltage at the control. It should read

21.6 to 30 Vdc.
Inspect all external wiring for secure

connections and verify insulation

integrity.
Verify the control lockout and operation

sequence, (Reference Startup/

Checkout section).
Observe a full operating cycle to prove

the sequence and timings are correct.
Replace any control that does not

meet listed specifi cations. Always

replace with the parts specifi ed by the

equipment manufacturer.
Replace a blown fuse with an

equivalent fast-acting automotive

blade style fuse (refer to Figure 1 for

fuse ratings and locations).