SECTION 3 - CHASSIS & TURNTABLE

3121259

– JLG Lift –

3-75

The Ground Module calculates the length of time the glow
plugs are energized prior to startup based upon ambient tem-
perature, engine coolant temperature, and battery voltage.
Refer to Table 3-6, Glow Plug Conditions.

The glow plugs are deenergized if:

• The Engine State is Engine Cranking, Engine Starting,

Engine running

or

• The Emergency Descent Mode is activated and Lift Down,

Tower Lift Down, or Jib Lift Down are active.

If the STARTER LOCKOUT option is enabled in the Machine
Setup, the Ground Module will not allow an engine start
attempt until the glow plug time has expired. If this option is
not enabled, the glow plug time can be interrupted and an
engine start attempt can be made. Starter Lockout is only
applicable for the first glow plug cycle.

Engine Speed Actuators

Engine speed on the Kubota engine is controlled by two actu-
ators; a throttle actuator that is On/Off operated (moves the
throttle arm between the Idle and High Engine positions) and
a proportional fuel rack actuator that limits the opening of the
fuel rack to control speeds between the Idle and High Engine
positions. The two actuators function together to achieve
smooth engine speed transitions. Refer to Table 3-7, Engine
Actuator Conditions.

ENGINE THROTTLE ACTUATOR

The Ground Module energizes the Throttle Actuator Relay
through terminal J1-2 if the engine is cranking or starting and
the Control System is calling for Idle RPM.

Table 3-6. Glow Plug Conditions

Engine Coolant

Temperature

Battery
Voltage

Ambient

Temperature

Glow Plug

Time On

Greater than or

equal to

122 º F (50 º C)

- -

- -

Off

- -

Less than 11V

- -

Off

Less than

122 º F (50 º C)

Greater than

11V

Greater than

59ºF(15ºC)

Off

Less than

122 º F (50 º C)

Greater than

11V

Temp Between

23ºF and 59ºF

(-5ºC and 15ºC)

On for

10 sec.

Less than

122 º F (50 º C)

Greater than

11V

Temp Between

5ºF and 23ºF

(-15ºC and -5ºC)

On for

15 sec.

Less than

122 º F (50 º C)

Greater than

11V

Temp Less

Than

5ºF (-15ºC)

On for

20 sec.

Table 3-7. Engine Actuator Conditions

Engine RPM

Level

Throttle

Actuator

Fuel Rack Actuator

Idle

Off

Energized/Fully Retracted

Between Idle RPM

and

High Engine RPM

On

Energized/Control Loop

High Engine

On

Energized/Fully Retracted

VBatt

J1-2 put

Out

30A Fuse

Throttle
Actuator

Throttle

Actuator Relay

Ground Module

-

+

Figure 3-58. Engine Throttle Actuator Schematic