Installation

(continued)

]

Test Shore Power

Connect the shore power cable to the shore power source. Turn

on the shore source to make power available to the boat.

a. Turn the selector switch to

SHORE. No Reverse

Polarity lights should be lit, and power available should

be indicated. If any red Reverse Polarity lights are on,

turn off the shore power circuit breaker and disconnect

the shore cord at the shore source. Either the hot and

neutral or hot and ground wires have been reversed.

Starting at the distribution panel, trace the connections

as far back as necessary to locate the error.

b. If there are no indications of reverse polarity, check to

see that power is available. If the electrical distribution

panel has a meter, verify that shore power is available

and at the proper voltage. If there is no meter, turn

on the load circuit breaker for an AC circuit powering

a convenience outlet and use a voltmeter to verify

that power is available from line to neutral at the plug.

Verify that there is no voltage between ground and

neutral.

]

Test Generator System

Turn the circuit breaker at the shore source to

OFF. Set the

selector switch to

OFF. The shore power available lights should

all be off. Start the generator and turn the generator breaker to

ON.

a. If there are power available lights for the generator

output, they should light.

b. There should be no power available indication at the

shore power circuit breaker.

c. Set the selector switch to

GENERATOR. Power

should be available at the power distribution panel. If

the electrical distribution panel has a meter, verify that

power is available and at the proper voltage.

d. There should be no power available lights indicating at

the shore circuit breaker.

]

Test the third source in a similar manner.

The Purpose of the AC Source Selector Switch

Alternating Current (AC) power changes polarity 60 times per second in the

US, Canada and Latin America and 50 times per second in Europe. This is

the frequency of the power and is referred to as Hertz (or the now outdated

term “cycle”). Because of this alternating nature of AC power, two live

sources of AC power, such as shore power and inverter power, or shore

power and a generator, cannot be electrically connected. The AC Source

Selector switch is designed to connect two sources of AC power to a

common circuit while preventing both sources from being connected to the

circuit simultaneously.

Useful Reference Books

• Calder, Nigel (2005). Boatowner’s Mechanical and Electrical Manual

(3d ed). Camden, ME: International Marine / McGraw-Hill.

• Wing, Charlie (2006). Boatowner’s Illustrated Electrical Handbook

(2d ed). Camden, ME: International Marine / McGraw-Hill.

Other Innovative Products from Blue Sea Systems

• 360 Panel System

• Battery management solutions

• AC and DC circuit protection devices

• WeatherDeck™ waterproof panels

• BusBars, fuses, and fuse blocks

• Analog and digital meters

It is possible to verify most connections using an ohmmeter before

power is applied. These procedures take a little time, but are

recommended, especially if some elements of a previous installation

might not have been clearly or correctly labeled or follow the expected

color codes.

There are many possible sources that may be selected using this

switch, and they may be arranged in any order. The following test

instructions are generally suitable for shore and generator installations.

The third source may be another shore power inlet

or an inverter or other specialized source.

]

Test Shore Connection to Switch

Disconnect the shore power cord from the shore power source

and bring the shore plug aboard to a point close to the switch

panel. Connect the other end of the shore cord to the boat’s

power inlet. Turn ON the shore power circuit breaker between the

inlet and the selector switch. Set the selector switch to OFF.

a. Use an ohmmeter to check for continuity from the shore

ground plug to the green wire at the electrical panel.

b. Check for continuity from the power cord plug neutral

pin to the neutral wire (white typically in US, light blue

typically in Europe) at the selector switch.

c. Check for continuity between the line pin of the shore

plug and the line wire (typically black in US, brown in

Europe) at the selector switch.

d. Check that there is a high resistance between (>1000

Ohms) the neutral conductor and the grounding

conductor.

e. Verify that there is a high resistance between (>1000

Ohms) between the shore cord plug neutral pin and

line pin. There may be indicator lamps in the circuit,

but no more than that with the selector switch in the off

position.

]

Verify Switch Selects Shore Input

With the shore cord still disconnected from the shore and

available onboard, and the generator set not operating, set the

load circuit breakers to off, so there is no load at the output side of

the selector switch.

a. Verify that the there is a high resistance between the

line and neutral of the load side terminals of the

selector switch. There may be indicator lamps still

attached, so it may not read open circuit.

b. Set the selector switch to SHORE. The ohmmeter

should still indicate a high resistance.

c. Short the line pin to the neutral pin of the shore cord

and verify that the line and neutral at the load side of

the selector show a low resistance when these are

shorted and a high resistance when they are not.

]

Verify the Generator Wiring

Turn the generator circuit breaker to OFF and set the selector

switch to the generator position. All load circuit breakers should

still be off. Leave the shore input circuit breaker in the on

position.

a. Verify that there is a high resistance (>1000 Ohms)

from the line to neutral.

b. Verify that there is a low resistance from the neutral to

ground at the load connections.

c. With the generator still not running, close the generator

circuit breaker at the generator. Verify that there is a

now a low resistance from line to neutral where the

generator windings are now connected across the

circuit.

d. Verify that there is still a high resistance from neutral to

ground and neutral to line at the shore power plug.

]

Test the third source in a similar manner.

]

Set the Selector switch to

OFF, turn the shore power breaker

to

OFF, and leave the load panel circuit breakers in the OFF

position. Complete the mounting of the switch.

]

Set your multimeter to volts.