Prepare site • assemble burner • mount burner, Inspect/repair/replace vent system, Combustion/ventilation air openings – Carlin EZ-1/2/3 User Manual

Page 5

Advertising
background image

Carlin part number MNEZ123 Rev. 07/13/11

– 5 –

Model EZ-1/2/3 oil burners — Instruction manual

2. Prepare site • assemble burner • mount burner

Inspect/repair/replace vent system

Do not install this burner unless you have verified the entire

vent system and the appliance are in good condition and
comply with all applicable codes. And ...

The vent and chimney must be sized and constructed in
accordance with all applicable codes.

Do not install or use an existing manual damper in the breech-
ing (vent connector) or chimney.

Do not connect the appliance vent connector to a chimney
or vent serving a fireplace, incinerator or solid-fuel-burning
apparatus.

In a cold climate, do not vent into a masonry chimney that
has one or more sides exposed to the outside. Install a listed
stainless steel liner to vent the flue products.

A defective vent system could result in severe personal injury,
death or substantial property damage.

Prepare vent/chimney

• Secure all metal vent joints with screws, following the vent manufac-

turer’s instructions. Seal all joints in the vent system and chimney.

Repair masonry chimney lining and repair all mortar joints as needed.

• Install a barometric draft regulator in the vent piping if specified in the

appliance manual. (The damper must be located in the same space

as the appliance.)

• Provide support for the vent piping. Do not rest the weight of any of the

vent piping on the appliance flue outlet.

Combustion/ventilation air openings

Even if combustion air is piped to an (optional) burner

air intake adapter, the boiler room must still have the

minimum air openings listed in Table 2 and described in the

following paragraphs. This is to provide needed ventilation to

keep the burner and appliance cool and to avoid the boiler

room developing negative pressure.

The combustion air openings MUST be sized based on the

total input of

all appliances in the room.

Check appliance manual and applicable codes for required sizing/design/

placement of combustion/ventilation air openings. You can use the follow-

ing general guidelines, taken from NFPA 31, provided they meet all local

requirements.

Louvers/screens

• Air opening sizes are always given in free area. This means after de-

duction for louver obstruction. If you can’t find the louver reduction for

the grilles used, assume free area is 20% of total for wood louvers, or

60% of total for metal louvers.

• Screens can be no finer than ¼-inch mesh, and must be accessible

for cleaning.

Residential installations

Unconfined spaces (at least 7,000 cubic feet per GPH)

• An unconfined space means a room with at least 7,000 cubic feet vol-

ume for each GPH input (or 50 cubic feet per MBH) of

all appliances

in the room. Example: For each 1 GPH oil input, the room must have

7,000 cubic feet (875 square feet with an 8-foot ceiling height.)

Table 2

Minimum combustion/ventilation air openings

• Open basements and crawl spaces are usually large enough, and will

generally allow enough air infiltration so special provisions will seldom

be required.

• If the building is tightly constructed, you will have to provide outside

air openings into the building. The total free area of the openings must

be at least 1 square inch per 5,000 Btuh (28 square inches per GPH)

of all appliances in the space.

• See Table 2 for summary.

Air openings to confined spaces

(less than 7,000 cubic feet per GPH)

• Air taken from inside building only —
• Provide two openings — one near floor, the other near ceiling. Provide

free area of 140 square inches per GPH input. If building is tightly

constructed, provide air opening(s) into building providing 30 square

inches per GPH as well.

• Air taken from outside —

• Direct through outside wall or vertical ducts: Provide two openings — one

near floor, the other near ceiling. Provide free area of 35 square inches

per GPH input.

• Through horizontal ducts: Provide two openings — one near floor, the other

near ceiling. Provide free area of 70 square inches per GPH input.

• Ventilation air from inside/combustion air from outside

Size openings to interior to provide 140 square inches free area per GPH input.

Size outside air duct to provide 28 square inches free area per GPH.

• See Table 2 for summary.

Source

of air

Mininimum

free area

of opening(s)

Total grill area, typical (sq. in.)

for firing rates of:

1 GPH

2 GPH

3 GPH

Wood Metal Wood Metal Wood Metal

Residential installations, unconfined spaces (7,000 cu. ft. volume per GPH)

From inside building,

typical construction

No special openings required if natural infiltriation is sufficient.

From inside building,

tight construction

1 or more grilles

30 Sq. in./ GPH

150

50

300

100

450

150

Residential installations, confined spaces

From inside building
through interior walls

2 openings, each
140 Sq. in./ GPH

700

234 1400 467 2100 700

From outside building
direct through outside
wall

2 openings, each
35 Sq. In./ GPH

175

59

350

117

525

175

From outside building
through vertical ducts

2 openings, each

35 Sq. In./ GPH

175

59

350

117

525

175

From outside building
through horizontal
ducts

2 openings, each

70 Sq. In./ GPH

350

117

700

234 1050 350

Ventilation through
interior walls, with an
opening to outside

2 Int. openings,
each
140 Sq. In./ GPH
1 Exterior opening
28 Sq. In./ GPH

700

140

234

47

1400

280

467

94

2100

420

700

140

Commercial installations

From outside building
direct through adjacent
outside wall

One opening through outside wall, providing free area of at least
28 Square inches per GPH input

Other conditions

Size openings per local codes/jurisdictions

Advertising