D I N L I N E I N S T A L L A T I O N I N S T R U C T I O N S

PAGE 13

product into a circuit which features a total
harmonic voltage ratio above 5%.

Model

Nominal

†Maximum

Voltage

Permissible

Abnormal

Over-Voltage

TDS-MT-277

220-277V

480V

TDS-MTU

220-277V

480V

MT275V-135K-A

220-240V

275V

Ensure that the correct voltage rating unit is
installed. Exceeding the nominal rating while
transient events occur may affect product life.

Note: Other voltage rating Movtecs are available. Refer

to Movtec table for actual ratings.

6. PROTECTION MODES

Movtecs are available in Three Mode and
Single Mode configurations. This refers to how
the internal protection is arranged and
applied to the circuit to be protected.

Three Mode units provide protection between
the Phase-Neutral*, Phase-Earth* and
Neutral-Earth circuit within one Movtec.

Single Mode units provide protection between
two conductors connected to the terminals
marked T1 and T2. These units can be
connected to provide protection from Phase-
Neutral* or Phase-Earth* or Neutral-Earth.
To allow the status indication and alarm
circuitry to operate, a neutral connection is
required for Phase-Earth* configured units,
and a Phase* connection is required for