D I N L I N E I N S T A L L A T I O N I N S T R U C T I O N S

PAGE 15

7. CONNECTION METHOD

To optimise transient performance, attempt to
connect the Movtecs in the “Preferred” fashion
as depicted on pages 16 and 17. This is
recommended for cable sizes between 6mm

2

and 16mm

2

. Take care not to run the protected

and unprotected wire parallel or in close
proximity.

Where this is not possible due to layout or
conductor size, use the “Non-preferred” “T”
connection method as depicted on pages 16 to
18. With this connection method, the “T” lead
should be between 6mm

2

and 16mm

2

. The

connection should be as short as practicable
(less than 100mm).

Cable sizes less than 6mm

2

should not be used

without specialist advice.

Ph

N

T1

T2

LINK
X3-X4

Ph

N

T1

T2

X4

T1

T2

X4

Ph

E

E

E

N

SINGLE MODE CONNECTIONS OPTIONS

PHASE

NEUTRAL

PROTECTION

PHASE

EARTH

PROTECTION

NEUTRAL

EARTH

PROTECTION