Connection method – ERICO TDS-MOVTEC Surge Diverters User Manual
Page 15

D I N L I N E I N S T A L L A T I O N I N S T R U C T I O N S
PAGE 15
7. CONNECTION METHOD
To optimise transient performance, attempt to
connect the Movtecs in the “Preferred” fashion
as depicted on pages 16 and 17. This is
recommended for cable sizes between 6mm
2
and 16mm
2
. Take care not to run the protected
and unprotected wire parallel or in close
proximity.
Where this is not possible due to layout or
conductor size, use the “Non-preferred” “T”
connection method as depicted on pages 16 to
18. With this connection method, the “T” lead
should be between 6mm
2
and 16mm
2
. The
connection should be as short as practicable
(less than 100mm).
Cable sizes less than 6mm
2
should not be used
without specialist advice.
Ph
N
T1
T2
LINK
X3-X4
Ph
N
T1
T2
X4
T1
T2
X4
Ph
E
E
E
N
SINGLE MODE CONNECTIONS OPTIONS
PHASE
NEUTRAL
PROTECTION
PHASE
EARTH
PROTECTION
NEUTRAL
EARTH
PROTECTION