Warnings – ERICO TDS-MOVTEC Surge Diverters User Manual

Page 4

Advertising
background image

G L O B A L L I G H T N I N G T E C H N O L O G I E S

PAGE 4

1. WARNINGS

• Prior to installation ensure that the

Movtec is of the correct voltage and
frequency, and is the type recommended for
the local power distribution, and for the
equipment being protected.

• Hazardous voltages may exist internally to

the units. The units should be installed
(and replaced) only by qualified personnel
in accordance with all relevant Electricity
Safety Standards.

• Do not power MPMs and three phase

connected Movtecs (Ph-N) without the
upstream neutral connected. Failure to do
so may damage the Movtecs and/or the
load.

• Where the MPMs/Movtecs are connected

to an earth, this must be a low impedance
earth (<10

Ω) for correct operation.

• X1-X4 connections may be at phase voltages

dependant upon connection method.

• If connecting to the Movtec alarm outputs

do not exceed the maximum permissible
ratings as damage may occur.

• Movtecs must be installed in an

enclosure or panel, ensure this does not
cause their environmental ratings to be
exceeded.

• Do not “Megger” or “Flash Test” circuits

with Movtecs installed.

• The DINLINE Surge Counter (DSC) should

not be used in voltage sensing mode with
TDS-Movtecs. Voltage sensing mode is not
compatible with TDS-Movtecs.

• All instructions must be followed to ensure

correct and safe operation.

• Diagrams are illustrative only, and should

not be relied on in isolation.