be connected to the mains
supply. The MPMs are not
intended for use as, nor are
they, a ‘switch
board’,
‘distribution board’ or other
equipment. As MPMs are
classified as ‘electrical
equipment’ (ie: a product),
AS 3000 Wiring Regulations
apply to the installation and
operation of the units.
In the multiple earth
neutral (MEN) distribution
system, the MPM equipment
should be installed as close
as possible after the MEN
point and after both the
main disconnect switch/
overcurrent protector and
any metering equipment.
TYPICAL CONNECTION DETAIL FOR MPM POINT-OF-ENTRY INSTALLATION
IN MEN DISTRIBUTION SYSTEM
METERING
MAIN
DISTRIBUTION
MPM
1
2
3
SUB
DISTRIBUTION
NEUTRAL
EARTH
M.E.N.
LINK