9 conductor length – ERICO TDS-DINLINE Surge Suppressor User Manual

Page 11

Advertising
background image

PAGE 11

9 CONDUCTOR LENGTH

To optimise transient performance, attempt to
connect units in the “Preferred” fashion as
depicted on pages 11 and 12. Some units have
double terminals to facilitate this. Take care
not to run parallel “protected” and
“unprotected” wiring.

Where this is not possible due to layout or
conductor sizing, use the “Non-preferred” “T”
connection method as depicted on page 13. With
this connection method, the “T” lead length
should be kept as short as practicable (less than
100mm) and wires should be bundled together.
The “T” conductor should be equal in size to the
main conductor, up to a maximum of 6mm

2

.

PREFERRED CONNECTION METHOD

Ph

Ph Ph

Ph Ph

Ph

INCORRECT

CORRECT

Separate wires

NON-PREFERRED CONNECTION METHOD

T1 T2

INCORRECT

CORRECT

Keep

Short

Keep Close

T1 T2