Tds-ar specifications – ERICO TDS-DINLINE Surge Suppressor User Manual

Page 24

Advertising
background image

PAGE 24

D S D I N S T A L L A T I O N I N S T R U C T I O N S

the wiring size used to connect to the TDS-AR
Ph & N terminals.

Australian regulations AS3000-1991, Table B2
specifies the following upstream protection for
single phase circuits, unenclosed in air.

Cable Size

HRC Fuse or CB

Rewirable Fuse

1.5mm

2

16A

12A

2.5mm

2

20A

16A

4mm

2

25A

20A

6mm

2

32A

25A

Where overcurrent protection of the
appropriate rating or smaller is already fitted
in the upstream circuit, overcurrent protection
at the TDS-AR will not be required.

TDS-AR SPECIFICATIONS:

Output Contact Ratings

Nominal switching capacity

2A 30VDC

Maximum switching power

60W 125VA

Maximum switching voltage

220VDC, 250VAC

Maximum switching current

2A

Input to output isolation

4kV

Note: TDS-AR operates on supply voltages

of 100-480V Vrms.

TDS-AR OVERCURRENT PROTECTION

The power supply to the TDS-AR circuit must
be provided with upstream overcurrent
protection. The fuse rating should be based on