Warnings – ERICO TDS-DINLINE Surge Suppressor User Manual

Page 4

Advertising
background image

PAGE 4

D S D I N S T A L L A T I O N I N S T R U C T I O N S

1. WARNINGS

• Prior to installation ensure that the unit is

of the correct voltage and frequency, and is
the type recommended for the local power
distribution, and for the equipment being
protected.

• Hazardous voltages may exist internally to

the modules. The units should be installed
(and replaced) only by qualified personnel
in accordance with all relevant Electricity
Safety Standards.

• Do not power three phase connected units

without the upstream neutral connected.
Failure to do so may damage the units and/
or the load.

• Where the unit has an earth terminal, this

must be connected to a low impedance earth
(<10

Ω) for correct operation.

• If connecting to the TDS Opto-coupler

alarm outputs do not reverse the +/-
connections or exceed the maximum
permissible ratings as damage may occur.

• Use only the TDS-AR Alarm Relay with

TDS-DINLINE.

• Use only TDS-SC Surge Counter with TDS

DINLINE.

• Units must be installed in an enclosure or

panel, ensure this does not cause the units
environmental ratings to be exceeded.

• Do not “Megger” or “Flash Test” circuits

with TDS-DINLINE units installed.

• All instructions must be followed to ensure

correct and safe operation.

• Diagrams are illustrative only, and should

not be relied on in isolation.