Voltage ratings, Protection modes – ERICO TDS-DINLINE Surge Suppressor User Manual

Page 8

Advertising
background image

PAGE 8

D S D I N S T A L L A T I O N I N S T R U C T I O N S

6. VOLTAGE RATINGS

Ensure that the correct voltage rating unit is
installed. Exceeding the nominal voltage
rating under transient conditions may affect
product life. Do not exceed the Maximum
Permissible Abnormal Over Voltage rating.

Maximum

Model

Nominal Voltage

Permissible

Abnormal

Over Voltage

TDS XXX-120

110-120 Vac

240Vac

TDS XXX-208

208 Vac

260 Vac

TDS XXX-240

220-240 Vac

415 Vac

TDS XXX-277

220-277 Vac

480 Vac

7. PROTECTION MODES

Protection Modes refers to how the internal
protection is arranged and applied to the
circuit to be protected.

TDS-DINLINE Surge Suppressors are Single
Mode units which provide protection between
two conductors connected to the terminals
marked T1 and T2. These units can be
connected to provide protection from Phase-
Neutral* or Phase-Earth* or Neutral-Earth.
To allow the status indication and alarm
circuitry to operate, a neutral connection is
required for Phase-Earth* configured units,
and a Phase* connection is required for
Neutral-Earth configured units.

*

Note. Some users may be used to the
terminology “Active” or “Line”, in place of
“Phase”. For consistency “Phase” is used
throughout this documentation.