5. MOUNTING

Surge Suppressors are designed to clip to
35mm top hat DIN rails (to Standard
EN50022). Unless otherwise mechanically
restrained, use horizontal DIN rails with the

Surge Suppressor fixing clip to the bottom, ie
label text the correct way up.

Units must be installed in an enclosure or
panel to provide the appropriate degree of
electrical and environmental protection.

Only use enclosures that:

• Do not cause the internal temperature to

exceed 55 deg C.

• Provide adequate electrical and safety

protection.

• Prevent the ingress of moisture and water.

• Allow Surge Suppressor Status Indication

to be inspected.