TABLE 24

APA RATED SHEATHING APPLIED DIRECT-TO-STUDS

(a)(b)

Minimum Nail

(c)

Minimum

Wood

Structural

Panel Span

Rating

Minimum

Panel

Performance

Category

Wall Stud

Spacing (in.)

Panel Nail Spacing

Maximum Wind Speed (mph)

Edges

(in. o.c.)

Field

(in. o.c.)

Wind Exposure Category

Shank

Diameter

(in.)

Minimum

Penetration

(in.)

B

C

D

0.113

1.5

24/0,

Wall-16 and

Wall-24

3/8

16

6

12

110

90

85

24/16,

Wall-24

7/16

16

6

12

110

100

90

6

150

125

110

0.131

1.75

24/16,

Wall-24

7/16

16

6

12

130

110

105

6

150

125

110

24 or less

6

12

110

90

85

(a) Panel strength axis parallel or perpendicular to supports. Three-ply

plywood sheathing with studs spaced more than 16" on center shall

be applied with panel strength axis perpendicular to supports.

(b) Table is based on wind pressures acting toward and away from

building surfaces, at 30-ft height in wall Zone 5 (corners) with

smallest effective area, per

Section 6.4.2.2 of ASCE 7-05

and

Section R301.2 of the 2009 IRC

, Stud specific gravity = 0.42.

(c) See

Table 5, page 14

, for nail dimensions.

TABLE 23

APA RATED LAP SIDING APPLIED DIRECT-TO-STUDS OR OVER STRUCTURAL SHEATHING

(a)(b)(c)

Minimum Nail

Shank Diameter

(d)

(in.)

Minimum

Performance

Category

Lap Siding

Fastener Spacing

(in.)

(e)

Lap Siding Width

(in.)

Maximum Wind Speed (mph)

Wind Exposure Category

B

C

D

0.113

3/8

6

6

130

110

100

8

110

90

85

12

85

NP

NP

(a) Table is based on wind pressures acting toward and away from

building surfaces, at 30-ft height in wall Zone 5 (corners) with

smallest effective area, per

Section 6.4.2.2 of ASCE 7-05

and

Section R301.2 of the 2009 IRC

, Stud specific gravity = 0.42.

(b) Recommendations of siding manufacturer may vary.

(c) Hot-dip galvanized nails are recommended for most siding applica-

tions, see Siding Fasteners section on page 48 for more information.

(d) See

Table 5, page 14

, for nail dimensions.

(e) Fastener spacing at top edge of lap siding.