Wall Construction

ENGINEERED WOOD CONSTRUCTION GUIDE

FORM NO. B360P

© 2011 APA – THE ENGINEERED WOOD ASSOCIATION

WWW.APAWOOD.ORG

46

TABLE 20

APA RATED LAP SIDING APPLIED DIRECT-TO-STUDS OR OVER NONSTRUCTURAL SHEATHING

(a)(b)(c)(d)(e)

Minimum Nail

(f)

Minimum

Performance

Category (in.)

Wall Stud

Spacing

(in. o.c.)

Lap Siding

Width (in.)

Maximum Wind Speed (mph)

Shank Diameter

(in.)

Penetration in

Framing (in.)

Wind Exposure Category

B

C

D

0.113

1.5

3/8

16

6

140

120

110

8

140

120

110

12

120

100

90

7/16

16

6

140

120

110

8

140

120

110

12

120

100

90

7/16

24

6

140

120

110

8

120

100

90

12

90

NP

NP

(a) Table is based on wind pressures acting toward and away from

building surfaces, at 30-ft height in wall Zone 5 (corners) with

smallest effective area, per

Section 6.4.2.2 of ASCE 7-05

and

Section R301.2 of the 2009 IRC

, Stud specific gravity = 0.42.

(b) Recommendations of siding manufacturer may vary.
(c) APA Rated lap siding rated 16 oc and 24 oc shall be used with

a maximum stud spacing of 16" o.c. and 24" o.c., respectively.

(d) Hot-dip galvanized nails are recommended for most siding applica-

tions, see

Siding Fasteners section of page 48

for more information.

(e) Supported panel joints shall occur approximately along the center-

line of framing with a minimum bearing of 1/2". Fasteners shall

be located 3/8" from panel edges. Siding installed over two or

more spans.

(f) See

Table 5, page 14

, for nail dimensions.

TABLE 21B

APA RATED SIDING (PANEL) APPLIED TO STRUCTURAL SHEATHING

(a)(b)(c)(d)(e)

APA Rated

Panel Siding

Minimum Nail

(f)(g)

Wall Stud

Spacing

(in. o.c.)

Panel Nail Spacing

Maximum Wind Speed (mph)

Shank Diameter

(in.)

Edges

(h)

(in. o.c.)

Intermediate

Supports

(in. o.c.)

Wind Exposure Category

B

C

D

3/8 Performance Category

APA MDO GENERAL

APA Rated Siding

16 oc or 24 oc

0.120 ring shank

16

6

12

110

90

85

6

125

105

90

24

6

12

90

NP

NP

6

110

90

85

(a) Table is based on wind pressures acting toward and away from

building surfaces, at 30-ft height in wall Zone 5 (corners) with

smallest effective area, per

Section 6.4.2.2 of ASCE 7-05

and

Section R301.2 of the 2009 IRC

, Stud specific gravity = 0.42.

(b) Recommendations of siding manufacturer may vary.
(c) For use as wood structural panel wall bracing, the minimum fas-

tener spacing of 6" o.c. at panel edges and 12" o.c. at intermediate

supports shall be sufficient.

(d) Hot-dip galvanized nails are recommended for most siding applica-

tions, see

Siding Fasteners section on page 48

for more information.

(e) Maximum stud spacing shall be in accordance with Table 21A.
(f) Ring shank nail shall be used.
(g) See

Table 5, page 14

, for nail dimensions.

(h) Supported panel joints shall occur approximately along the center-

line of framing with a minimum bearing of 1/2". Fasteners shall be

located 3/8" from panel edges.

TABLE 21A

MAXIMUM STUD SPACING: APA RATED SIDING (PANEL) APPLIED DIRECT-TO-STUDS OR STRUCTURAL SHEATHING

Siding Description

Minimum Performance

Category or

Span Rating

Maximum Stud Spacing (in.) for Vertical Rows of Nails

Parallel to Supports

Perpendicular to Supports

APA MDO GENERAL

3/8

16

24

15/32

24

24

APA Rated Siding

16 oc

16

16

(a)

24 oc

24

24

(a) Stud spacing may be 24" o.c. for veneer-faced siding panels.