Georgia-Pacific APA Engineered Wood Construction Guide - Walls User Manual

Page 9

Advertising
background image

Wall Construction

ENGINEERED WOOD CONSTRUCTION GUIDE

FORM NO. B360P

© 2011 APA – THE ENGINEERED WOOD ASSOCIATION

WWW.APAWOOD.ORG

50

Leave 1/8" spacing and caulk vertical joints unless otherwise

recommended by siding manufacturer

Building paper or other code-recognized weather-resistive

barrier required

APA RATED SIDING (lap siding), maximum width 12".

Minimum headlap 1".

FIGURE 10

APA STURD-I-WALL (Horizontal Lap Siding Installation)

(a)

6" minimum clearance, siding to grade

1-1/2"-wide starter strip, thickness to match lap siding

(a) For engineered shear wall segments or wall bracing requirements, use APA Rated Sheathing

for wall sheathing under lap siding (

see Figure 12

). Other methods permitted by model building

codes for braced wall segments may also be used.

1/8" spacing is recommended at all edge and end joints

unless otherwise indicated by panel manufacturer

Building paper or other code-recognized weather-resistive barrier required

APA RATED SIDING panels applied over sheathing

FIGURE 11

APA RATED SIDING (PANEL SIDING) OVER WOOD STRUCTURAL PANEL SHEATHING

6" minimum clearance, siding to grade

Panel siding or APA RATED SHEATHING meets code requirement for wall bracing

Leave 1/8" spacing and caulk vertical joints, unless otherwise

recommended by siding manufacturer

Building paper or other code-recognized weather-resistive barrier required

APA RATED SIDING (lap siding), maximum width 12". Minimum headlap 1".

FIGURE 12

APA RATED SIDING (LAP SIDING) OVER WOOD STRUCTURAL PANEL SHEATHING

6" minimum clearance, siding to grade

1-1/2"-wide starter strip, thickness to match lap siding

APA RATED SHEATHING meets code requirement for wall bracing

Siding joints, if staggered may occur away from studs with nailable sheathing