29. S-ALARM

Select the level and control channels triggered by the security alarm input.

When a contact is sensed on the security alarm input, selected control channels will

cycle on and off at a 1 hertz rate. The level of the on cycle can be set from 0% to

100%. The security alarm input takes precedence over the DMX and analog inputs.

The system will stay in security alarm mode until the contact is removed.

Press EXECUTE to enter the menu and configure the security alarm input.

L>FL:01*

Displays the output level (L>FL) of 100% and control channel (01*).

L>00:01*

Press MENU (

) to change the output level from 00% to 100% (FL).

L>FL:01*

Press MENU (

) at the same time to toggle the level back to 100% (FL).

L:FL>01*

Press EXECUTE to toggle the pointer (>) and select the control channel(s).

L:FL>24*

Press MENU (

) to select the desired control channel from 01 to 24.

L:FL>24

Press EXECUTE to toggle the flag (*) for each desired control channel.

Press ESCAPE to exit the menu and save the desired settings.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 2 minutes of inactivity and save.

30. F-ALARM

Select the level and control channels triggered by the fire alarm input.

When a contact is sensed on the fire alarm input, the selected control channels are

triggered on to the selected output level from 0% to 100%. The fire alarm input is

merged with the DMX and analog inputs with highest takes precedence (HTP). The

system will stay in fire alarm mode until the contact is removed.

Press EXECUTE to enter the menu and configure the fire alarm input.

L>FL:01*

Displays the output level (L>FL) of 100% and control channel (01*).

L>00:01*

Press MENU (

) to change the output level from 00% to 100% (FL).

L>FL:01*

Press MENU (

) at the same time to toggle the level back to 100% (FL).

L:FL>01*

Press EXECUTE to toggle the pointer (>) and select the control channel(s).

L:FL>24*

Press MENU (

) to select the desired control channel from 01 to 24.

L:FL>24

Press EXECUTE to toggle the flag (*) for each desired control channel.

Press ESCAPE to exit the menu and save the desired settings.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 2 minutes of inactivity and save.

31. Ø-PATCH

Set the zero-cross phase reference for each dimmer output circuit.

Each of the 24 dimmer control outputs can be patched to any of the incoming phase

references. The phase reference for each dimmer control output must be the same

as the incoming phase for the dimmer. If a dimmer control output is patched to the

incorrect phase reference the dimmer will not dim correctly and will go to full output at

around 1% DMX input.

The factory configuration for DE90-3000 Series retrofit control systems is for three-

phase applications. The defaults (DEFAULTS) menu is used to reconfigure the phase

patch for standard single-phase applications.

Refer to the charts on page 8 for the standard Ø-PATCH configuration for DE90

dimmer racks.

This menu provides the ability to configure a custom Ø-PATCH for non-standard

applications.

Press EXECUTE to enter the menu and configure the dimmer phase patch.

CH 01 ØA

Displays the dimmer output channel (CH 01) and patched phase (ØA).

CH 24 ØA

Press MENU ( ) to change the dimmer output channel to patch from 01 to 24.

CH 24 ØB

Press EXECUTE to toggle the patch to phase-B (ØB).

CH 24 ØC

Press EXECUTE to toggle the patch to phase-C (ØC).

Press ESCAPE to exit the menu and save the desired settings.

Press RESET to exit the menu without saving.

The menu will automatically timeout after 2 minutes of inactivity and save.