2 c112 setting for a double thermocouple, 3 c113 unit, decimal place, 4 c114 device function – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Operating Manual User Manual
Page 25: C112 setting for a double thermocouple, C113 unit, decimal place, C114 device function, 7 configuration level

7 Configuration level
23
7.2
C112 Setting for a double thermocouple
7.3
C113 Unit, decimal place
7.4
C114 Device function
Double thermocouple
Comment
0
no
sensor short circuit not detected!
1
yes
only available for C111 from 037 to 048
v
Chapter 7.1 “C111 Analog inputs”
Can detect a sensor short circuit
Unit, decimal place
Comment
0
°C, no decimal place
1
°C, one decimal place
2
°F, no decimal place
3
°F, one decimal place
Device function
Comment
0
Initial commissioning of TB
temperature limiter
Whatever the switching state of the relay before the power failure, the TB
remains locked when the power returns.
1
Temperature limiter TB
Release is only necessary if the temperature is exceeded
2
Temperature monitor TW
Automatic release
A
When the unit changes to °F, the measurement is
converted. All other measurement-related values,
such as AL, are unchanged!