12 error messages, Error messages – JUMO 14597 safetyM TB/TW - Temperature Limiter and Temperature Monitor Operating Manual User Manual
Page 46

12 Error messages
44
12 Error
messages
Error display (code)
Cause
Remedy
The total number of relay switching
operations has been reached.
h
Increase the total number of relay switching
operations
v
Chapter 7.11 “C 120 Limit value for relay
h
Acknowledge with the Reset key
v
Chapter 7.12 “C 121 Count for relay switching
0002
Terminal temperature
is outside the -10 to 80°C range
h
Check the ambient temperature
h
Acknowledge with the Reset key
If that does not help, send the instrument in
0003
Reference voltage
The measured value is above 999 or below
-999 and is thus outside the 3-digit display
range.
-
A/D converter error
h
Acknowledge with the Reset key
If that does not help, send the instrument in
0004
Calibration constant
The instrument must be returned to JUMO for repair.
h
Send the instrument in
v
Chapter 2.1 “Service addresses”
0005
Configuration data
Value cannot be displayed (too large or too
small)
0006
reserved
-
0007
reserved
-