Connection diagram dimensions block diagram, Function – JUMO 902910 CANtrans T RTD Temperature Probe with CANopen Output Data Sheet User Manual

Page 3

Advertising
background image

2010-06-11/00418901

Data sheet 90.2910

Page 3/4

JUMO GmbH & Co. KG
Delivery address: Mackenrodtstraße 14,

36039 Fulda, Germany

Postal address:

36035 Fulda, Germany

Phone:

+49 661 6003-0

Fax:

+49 661 6003-607

E-mail:

[email protected]

Internet:

www.jumo.net

JUMO Instrument Co. Ltd.
JUMO House
Temple Bank, Riverway
Harlow - Essex CM20 2DY, UK
Phone: +44 1279 63 55 33
Fax:

+44 1279 63 52 62

E-mail:

[email protected]

Internet: www.jumo.co.uk

JUMO Process Control, Inc.
8 Technology Boulevard
Canastota, NY 13032, USA
Phone:

315-697-JUMO
1-800-554-JUMO

Fax:

315-697-5867

E-mail:

[email protected]

Internet: www.jumo.us

Connection diagram

Dimensions

Block diagram

Type 902910/10

Type 902910/12

Function

(1)

The measured temperature value is dig-
itized.

(2)

The temperature signal is digitally facto-
ry adjusted.

(3)

The probe monitoring system perma-
nently checks the correct function of
the probe signal and initiates high-prior-
ity emergency telegrams in the event of
an error.

(4)

The measured temperature value can
be scaled to any measuring unit (or as
% of the measuring range).

(5)

The precise adjustment has a freely set-
table characteristic curve offset.

(6)

Undesirable signal fluctuations can be
suppressed using the configurable filter
constant.

(7)

The measured value is transmitted with
a freely selectable decimal place.

(8)

The measuring range monitoring has
freely selectable upper and lower limits.
The result is transmitted as a status
byte in addition to the measured value
in the PDO telegram.

(9)

The fly back function saves the mini-
mum and maximum measured temper-
ature value.

(10)

Date and name of the last maintenance
work can be saved.

(11)

The emergency telegram is initiated in
the event of a defective probe.

(12)

The PDO telegram contains the 32 bit
measured value and the 8 bit status.
The measured value output can be con-
trolled via various trigger conditions.

(13)

SDO telegrams can be used to set pa-
rameters as well as request measured
values and the status.

(14)

The heartbeat signal can be used to ad-
ditionally monitor the function of the
transducer.

(15)

The Sync command can be used to ad-
ditionally control measured value trans-
mission.

(16)

The NMT telegrams serve to control the
operating status of the transducer.

(17)

The CAN module ID and the CAN baud
rate are set optionally via LSS or SDO.