6 electrical installation, 1 important notes, Electrical installation – Lenze SDSGS User Manual

Page 30: Important notes, 6electrical installation

Advertising
background image

Electrical installation

Important notes

6

l

30

BA 13.0011−EN 1.0

6

Electrical installation

6.1

Important notes

{

Danger!

Hazardous voltage on the power connections even when disconnected from
mains: residual voltage >60 V!
Before working on the power connections, always disconnect the drive
component from the mains and wait until the motor is at standstill.
Verify safe isolation from supply!

(

Stop!

Electrical connections must be carried out in accordance with the national and
regional regulations!

ƒ

The connection must ensure a permanent and safe electrical supply, i.e.
– no loose wire ends,
– use assigned cable end fittings,
– establish a safe PE conductor connection,
– Tighten the plug−in connector to the limit stop.

ƒ

The smallest air gaps between uncoated, live parts and against earth must not fall
below the following values:

Minimum requirements for basic
insulation according to IEC/EN
60664−1 (CE)

Higher requirements for UL design

Motor diameter

3.87 mm

6.4 mm

< 178 mm

ƒ

All unused cable entries must be sealed against dust and water.

Voltage supply

ƒ

Inverter−optimised motors
– must be supplied by inverters.
– connect the encoders mounted to the motor with the corresponding connections

of the inverter.

ƒ

Holding brake (as option)

ƒ

Follow the Operating Instructions for the inverter used to connect it.