Installation, 3installation, 1 mechanical installation – Lenze SV SMV additional I-O module User Manual

Page 7: Alsv01b 4

Advertising
background image

ALSV01B

4

Installation

3

Installation

3.1 Mechanical Installation

1. Ensure that for safety reasons the AC supply has been disconnected before opening the terminal

cover.

2. Insert the Additional I/O module in the terminal cover and securely “click” into position as illustrated

in Figure 2.

3. Wire the cables to the connector provided and plug the connector into the option module.
4. Align terminal cover for re-fitting, connect the module umbilical cord to the drive then close the cover

and secure, as shown in Figure 3.

13G

13F

21

20

19

7mm

<_ 2.8 mm²
(12-22 AWG)

0.5 Nm/ 4.5 lb-in

13G

13F

21

20

19

7mm

<_ 2.8 mm²
(12-22 AWG)

0.5 Nm/ 4.5 lb-in

Red wire and black wire
are present in the ESVZAL1
module. They are not
present in the ESVZAL0
module. Refer to wiring
instructions below.

Figure 2a: NEMA 1 (IP31) Installation

Figure 2b: NEMA 4X (IP65) Installation

The ESVZAL1 I/O Option Module
contains 1 red wire and 1 black wire
that must be wired into the standard
SMVector Inverter terminal strip.

Connect the black wire to terminal #2.

Connect the red wire to terminal #11.

Refer to adjacent diagram.

1

2

5

6 25 4 11 13A 13B 13C 14 30 16 17

Black and Red wires from ESVZAL1 Module

Terminal Strip of Standard SMVector Inverter

Figure 2c: Wiring the ESVZAL1 I/O Module

Advertising