ALSV01B

6

Installation

3.3 Electrical Installation

3.3.1 Terminal Description

Table 3 contains each terminal's electrical specification and any parameter description associated with
that terminal.

Table 3: Additional I/O Module Specifications

Terminal

Function

Description

19

Relay N.O.

Relay output configurable with P441, P144

AC 250 V / 3 A 17 DC 24 V / 2 A … 240 V / 0.22 A, non-inductive

20

Relay Common

21

Relay N.C.

13F

Digital Input

13F configurable with P426

13G configurable with P427

Input Impedance = 4.3 kohm

The assertion level of Terminals 13F and 13G will match the assertion level of

the standard SMVector digital inputs 13A, 13B, 13C, etc…

Refer to the description of P120 and Terminal #4 in the SMVector - Frequency

Inverter Operating Instructions (SV01)

13G

Digital Input

NOTE
For ESVZAL0:
Control and communications terminals provide reinforced insulation when the drive is connected to a power system
rated up to 300V between phase to ground (PE) and the applied voltage on terminals 19, 20 and 21 is less than 250
VAC between phase and ground (PE)
For ESVZAL1:
Control and communications terminals provide reinforced insulation when the drive is connected to a power system
rated up to 300V between phase to ground (PE) and the applied voltage on terminals 19, 20 and 21 is less than 150
VAC between phase and ground (PE)
Control and communications terminals provide basic insulation when the drive is connected to a power system
rated up to 300V between phase to ground (PE) and the applied voltage on terminals 19, 20 and 21 is less than 250
VAC between phase and ground (PE).

3.3.2 Module Wiring

Figure 5 illustrates the wiring of the ESVZAL0 and ESVZAL1 modules.

19 20

21

19 20

21 13F 13G

To SMVector Control

Terminal Strip TB#4

Figure 5a: ESVZAL0

Figure 5b: ESVZAL1

NOTE
To assert terminals 13F and 13G with external power
sources, refer to section 3.2.3 of the SMVector
Operating Instructions (SV01)

Advertising