EDKZS3Y200 DE/EN/FR/ES/IT 1.1

The following must be observed when using sinusoidal filters:

ƒ

Use sinusoidal filters only together with standard asynchronous machines 0 ... 550 V.

ƒ

Operation is only permissible using a V/f or V/f

2

characteristic control.

ƒ

Operation is only permissible using a switching frequency of 2 ... 4 kHz.

Ensure that the automatic switching frequency reduction is deactivated (see
documentation of the standard device).

ƒ

Limit the output frequency to maximally 150 Hz.

ƒ

Please note when dimensioning the controller that the controller has an additional load
of 10 ... 15 %.