Electrical installation – Lenze EZS3-xxxA200 Sinusoidal filter 115-150A User Manual
Page 19
Electrical installation
Mounting steps
l
19
EDKZS3Y200 DE/EN/FR/ES/IT 1.1
4.3
Mounting steps
M
3~
1U1
1U2
1V1
1V2
1W1
1W2
EZS3-xxxA200
xxxx
U
V
W
SSP94SF107
SSP94SF004
SSP94SF109
x
Stripping length depends on the filter size
How to connect the filter:
1. Loosen the four screws
0 and remove the terminal cover 1.
2. Connect the filter input cable to terminals 1U1, 1V1, 1W1.
Connect the filter output cable to terminals 1U2, 1V2, 1W2.
–
Use shielded cables.
–
Connect the two PE conductors to the PE stud using ring cable lugs
(PE connection must comply with EN 50178).
–
Observe tightening torques.
3. Turn down the shield and connect it to the shield sheet (PES) with a surface
as large as possible.
–
Fix the shield with a metal cable tie or hose clip
2.
–
Use an additional cable tie for strain relief
3.
4. Insert the terminal cover
1 and fix it with four screws 0.