2 technical data, Technical data 2, 2technical data – Lenze EZS3-xxxA200 Sinusoidal filter 115-150A User Manual

Page 15

Advertising
background image

Technical data

2

l

15

EDKZS3Y200 DE/EN/FR/ES/IT 1.1

2

Technical data

Standards

Conformity

CE

Low−Voltage Directive

Approval

UR

UL508, Industrial Control
Equipment, Underwriter
Laboratories (File−No. E219022) for
USA and Canada

Operating conditions

Climatic conditions

Class 3K3 according to EN 50178

Without condensation, average
relative humidity 85 %

Permissible ambient
operating temperature

−10 °C ... +55 °C
Above 40 °C, the rated current I

r

must be reduced by 2.5 %/°C

Permissible installation
height

0 ... 4000 m amsl
Above 1000 m, the rated current I

r

must be reduced by 5 %/1000 m

Vibration resistance

Accelerational stability up to 1 g

EN50178, IEC61800−5−1 and
Germanischer Lloyd, general
conditions

Degree of protection

IP20 (protection against contact to NEMA 250 type 1)

Mounting position

Vertical with fixing bracket below

Connecting cables

Controller

« filter

As short as possible, shielded

Filter

« motor Max. 200 m shielded or max. 300 m unshielded

Rated data

Type

U

[V]

f

ch

[kHz]

I

r

[A]

P

V

[W]

L

[mH]

m

[kg]

EZS3−115A200

0 ... 550 V AC

2 ... 4

115

360

0.7

66

EZS3−150A200

150

400

0.5

69

U

Voltage range

PV

Power loss

f

ch

Switching frequency

L

Inductance

I

r

Rated current

m

Mass

Advertising