Electrical installation

Important notes

6

48

EDK94AZMP DE/EN/FR/ES/IT 7.0

6

Electrical installation

6.1

Important notes

ƒ

Installation must

always be in accordance with the operating conditions specified in the

Technical data ( 38).

be carried out to EN 60204-1.

ƒ

Please observe the following when selecting the cable type:

The cables used must comply with the approvals required for the

application (e. g. VDE, UL etc.).

Fuses and cable cross-sections must be dimensioned in accordance with

the specifications in the documentation for the basic device.

Danger!

Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains

disconnection.
Possible consequences:

ƒ

Death or severe injuries when touching the power terminals.

Protective measures:

ƒ

Switch off the power supply and wait for at least three minutes

before working on the power terminals.

ƒ

Make sure that all power terminals are deenergised.

Danger!

Dangerous voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:

ƒ

Death or severe injuries when the device is touched in the event

of a fault.

Protective measures:

ƒ

Implement the actions required in the EN 61800-5-1. Especially:

– Fixed installation

– PE connection must conform to standards (PE conductor

diameter  10 mm

2

or PE conductor must be connected twice)