Mechanical installation – Lenze E94AZRP0824 User Manual

Page 52

Advertising
background image

Mechanical installation

Mounting steps

5

52

EDK94AZRP45 DE/EN/FR/ES/IT 5.0

Use with 9400
Proceed as follows for the installation:
1. Prepare M5 threaded holes on the mounting plate, for instance according

to the mounting grid.

–

Always use all mounting points specified.

2. Screw the filter onto the mounting plate.

–

Use M5 screw and washer assemblies or M5 hexagon socket screws

with washers.

–

If further devices are to be mounted directly adjacent on the right-hand

side of the filter, do not tighten the screws fully before all devices are

mounted and aligned.

–

Tightening torque: 3.4 Nm (30 lb-in).

Use with i700
How to proceed during mounting:
1. Prepare M5 threaded holes on the mounting plate.

–

Always use all fixing points specified.

2. Screw the filter to the mounting plate.

–

Use M5 screw and washer assemblies or M5 hexagon socket screws

with washers.

–

Tightening torque: 3.4 Nm (30 lb-in).