Electrical installation

Mounting steps

6

59

EDK94AZRP45 DE/EN/FR/ES/IT 5.0

Use with 9400
How to connect the filter:
1. Connect filter output cables (X302/L1’, L2’, L3’, PE’) to power supply

module.

2. Remove cover .

3. Use ring cable lugs to bolt mains cables onto threaded bolts X301/L1, L2,

L3.

–

Observe tightening torque! ( 57)

4. Use ring cable lug to bolt mains-side PE conductor onto threaded bolt

X301/PE.

–

Observe tightening torque! ( 57)

–

PE connection must comply with EN 61800-5-1 .

5. Use cable binders to fix all mains-side cables at strain relief sheet .

6. Assemble cover .

–

The filter must not be commissioned without cover !

Use with i700
How to connect the filter:
1. Connect filter output cables (X302/L1’, L2’, L3’, PE’) to power supply

module.

–

Cable ends (cable lugs) may be removed.

–

Cable lengths may be shortened, if required.

–

Do not use wire end ferrules for connecting filter output cables to the

i700 supply terminal.

2. Remove cover .

3. Use ring cable lugs to bolt mains cables onto threaded bolts X301/L1, L2,

L3.

–

Observe tightening torque! ( 57)

4. Use ring cable lug to bolt mains side PE conductor onto threaded bolt

X301/PE.

–

Observe tightening torque! ( 57)

–

PE connection must comply with EN 61800-5-1.

5. Use cabke binders to fix all mains side cables on strain relief sheet .

6. Assemble cover .

–

The filter must not be commissioned without cover !