Commissioning
Commissioning for 8200 series standard devices
EDKMF2102 DE/EN/FR 7.1
76
l
inbetriebnahme82XXvector
Detailed
information
Procedure
Step
It is now possible to communicate with any controller, i.e. all codes can be read and all writable codes
can be changed.
4.
Make other necessary controller settings.
W Commissioning of the controller
Documentation
for the respective
controller
l
Select the frequency setpoint with C0046 and the control word
with C0135.
l
Set the operating mode C0001 = 3.
l
With speed setpoint = 0, quick stop (QSP) is active in this
operating mode at switch−on. This prevents uncontrolled starting
of the controller.
– Deactivation of the QSP function: Set C0135/bit 3 = 0 (FALSE).