Electrical installation

Voltage supply

6

EDK2191DB DE/EN/FR 2.0

35

l

H2_SpgVersorgg−Steckerleiste_Schraubanschl_15

External voltage supply

)

Note!

In the case of an external voltage supply and for greater distances between the
control cabinets, always use a separate power supply unit (SELV/PELV) that is
safely separated in accordance with EN 61800−5−1 in each control cabinet.

The external voltage supply of the communication module ...
ƒ is required if communication via the fieldbus is to be continued when the supply of

the device fails.

ƒ is provided via the 2−pin terminal strip with screw−type connection (24 V DC):

Terminal

Description

+

External voltage supply
U = 24 V DC (20.4 V − 0 % ... 28.8 V + 0 %)
I = 85 mA

Reference potential for external voltage supply

ƒ The parameters of a standard device disconnected from the mains cannot be

accessed.

Terminal data

Area

Values

Electrical connection

Plug connector with screw connection

Possible connections

rigid:

1.5 mm

2

(AWG 16)

flexible:

without wire end ferrule
1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve
1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve
1.5 mm

2

(AWG 16)

Tightening torque

0.5 ... 0.6 Nm (4.4 ... 5.3 lb−in)

Stripping length

6 mm