8 diagnostics, Diagnostics, 8diagnostics – Lenze EMF2191IB User Manual

Page 38

Advertising
background image

8

Diagnostics

EDK2191DB DE/EN/FR 2.0

38

l

H1_Diagnose−−−−(DUMMYSEITEVOR)−−−

8

Diagnostics

The LEDs on the front are provided to the communication module for the purpose of fault
diagnostics.

LED

Description

Pos.

Colour

Condition

0

green

off

The communication module is supplied with voltage, but has no
connection to the basic device (basic device is either switched off,
in the initialisation phase, or not available).

on

The communication module is supplied with voltage and is
connected to the standard device.

1

green

The NMT state machine triggers the two−colored LED:

l

Green: Display of status messages

l

Red: Display of error messages

off

NMT_GS_OFF, NMT_GS_INITIALISATION,
NMT_CS_NOT_ACTIVE / NMT_MS_NOT_ACTIVE

NMT_CS_PREOPERATIONAL_1 / NMT_MS_PREOPERATIONAL_1
(LED flashes once within a second.)

NMT_CS_PREOPERATIONAL_2 / NMT_MS_PREOPERATIONAL_2
(LED flashes twice within a second.)

NMT_CS_READY_TO_OPERATE / NMT_MS_READY_TO_OPERATE
(LED flashes three times within a second.)

NMT_CS_BASIC_ETHERNET
(LED is blinking with a frequency of 10 Hz or depending on the
connection state)

NMT_CS_STOPPED
(LED is blinking with a frequency of 2.5 Hz.)

NMT_CS_OPERATIONAL / NMT_MS_OPERATIONAL
(LED is lit permanently.)

red

ERROR
(LED is lit permanently. An error has occurred.)

2

red

on

The red and green drive LED indicates the operating status of the
standard device (see documentation of the standard device).

3

green

blinking

Depending on the connection state, the data is transmitted or
received (ACTIVITY).

4

yellow

on

Ethernet connection is available (LINK).

Advertising