Protective insulation, Connection terminals, Technical data – Lenze E82ZAFCC200 User Manual

Page 45

Advertising
background image

Technical data

Protective insulation

4

EDK82ZAFCC-200 DE/EN/FR 4.0

45

H2 Schutzisolierung-INS_Klembesch

Protective insulation

Insulation between bus and ...

Type of insulation (in accordance with

EN 61800-5-1)

Power section

– 8200 vector

Reinforced insulation

– 8200 motec

Reinforced insulation

Reference earth / PE (X3/7)

Functional insulation

Supply for CINH (X3/20)

Functional insulation

Controller inhibit, CINH (X3/28)

Functional insulation

Connection terminals

Terminal

X3/

Designation

Function / level

39

GND2

Reference potential 2 of the controller inhibit (CINH) at X3/28

28

CINH

Controller inhibit

Input resistance: 3.3 k

Start = HIGH (+12 ... +30 V DC)
Stop = LOW (0 ... +3 V DC)
Reference: GND2

External supply with U

ext

= +12 V DC - 0 % ... +30 V DC + 0 %

Internal supply via terminal X3/20

7

GND1

Reference potential 1

LO

CAN-LOW

CAN data line (LOW)

HI

CAN-HIGH

CAN data line (HIGH)

E1, E2

Digital inputs

User-defined

Input resistance: 3.3 k

0 = LOW ( 0 ... +3 V) PLC level, HTL
1 = HIGH (+12 ... +30 V) PLC level, HTL
Reference: GND2

E1 can optionally also be used as frequency input (0 ... 10 kHz,
single-track or 0 ... 1 kHz two-track, configuration via C0425).

20

Voltage source for internal supply

U

int

= +20 V DC

I

max

= 30 mA

Reference: GND1

Advertising