Possible settings via DIP switch

EDK82ZAFCC-200 DE/EN/FR 4.0

58

H1inbet-Baudrate

Baud rate setting

ƒ The baud rate must be identical for all CAN nodes.
ƒ The following baud rates can be set:

Baud rate [kbps]

Switch

7

8

9

20

ON

OFF

ON

50

OFF

ON

ON

125

OFF

ON

OFF

250

OFF

OFF

ON

500

OFF

OFF

OFF

Note!

Switch off the voltage supply of the function module / standard device and
then switch it on again to activate the changed settings.