Electrical installation

Important notes

EDKMF2176X DE/EN/FR 4.2

16

H1_E_INST-2176_service_BL

6

Electrical installation

Important notes

Danger!

Improper handling of the CAN repeater and the basic device can cause severe

injuries to persons and damage to material assets.
Observe the safety instructions and residual hazards mentioned in the

instructions for the basic device.

Stop!

The following items must be observed for trouble-free operation of the CAN

repeater:

ƒ

The baud rate must be identical in both CAN segments!
In case of different baud rates, the entire bus system fails (”BUS-OFF”

state).

ƒ

Wire the system carefully!
If the CAN cables are crossed in a segment, the entire bus system fails

(”BUS-OFF” state).

ƒ

Do not exceed a bus load of 80 %!

Terminal data

Electrical connection

Plug connector with screw connection

Possible connections

rigid: 1.5 mm

2

(AWG 16)

flexible:
without wire end ferrule

1.5 mm

2

(AWG 16)

with wire end ferrule, without plastic sleeve

1.5 mm

2

(AWG 16)

with wire end ferrule, with plastic sleeve

0.5 mm

2

(AWG 20)

Stripping length

6.5 mm