background image

Technical data

General data and operating conditions

EDKMF2176X DE/EN/FR 4.2

19

H1_Daten-2176_Anschlussdaten

7

Technical data

General data and operating conditions

General data
Characteristics

z

CAN1 and CAN2 disconnected from the current supply via

DC/DC converter

z

CAN1 isolated from CAN2 via optocoupler

z

CAN terminating resistors integrated in CAN1 and CAN2

Interface

CAN bus interface

ISO/IS 11898-2 (Philips 82C251 transceiver)

Baud rate

Up to 500 kBit/s

Signal propagation delay

within the repeater

Approx. 150 ns from CAN1 to CAN2,

i. e. the max. bus length decreases by approx. 30 m

Housing

Plastics DIN rail housing

Ambient conditions
Climatic conditions

Storage

-25 °C … +60 °C

Transport

-25 °C … +70 °C

Operation

-20 °C … +60 °C

Degree of pollution

2 according to EN 50178

Enclosure

IP20

Mounting conditions
Mounting type

Mounting on 35 × 7.5 mm DIN rail

Connection data

Connection data
Connections

Screw terminals

Voltage supply

DC 24 V (+9 … +35 V)

Power input

DC 24 V, 1.5 W typ.