background image

Electrical installation

Design as isolation

EDKMF2176X DE/EN/FR 4.2

17

H1_E_INST-2176_service_BL

Design as isolation

Function
The CAN repeater automatically separates from a segment if the segment shows a

permanent disturbance level of +1 V ... +5 V between CAN-HI and CAN-LO. The

corresponding red LED is on. The other segment goes on working.
If the permanent disturbance level has disappeared, the segment is connected to the

system again through the CAN repeater.
Basic circuit diagram

HI

HI

LO

LO

GND

GND

HI

HI

LO

LO

GND

GND

CAN 2.1

CAN 1.1

HI

HI

LO

LO

GND

GND

HI

HI

LO

LO

GND

GND

CAN 2.n

CAN 1.n

+24 V DC

(+9 ... +35 V DC)

CAN2

CAN1

2176

+24 GND

HI LOGND

HI LOGND

120

120

=

120

120

2176_002

CAN 1.1 … CAN 1.n

Nodes in segment CAN1

CAN 2.1 … CAN 2.n

Nodes in segment CAN2

A total of max. 63 nodes possible