4electrical installation – Lenze E82ZAFAC001 User Manual

Page 36

Advertising
background image

4

Electrical installation

EDK82ZAFAC−001 DE/EN/FR 5.0

36

l

INS_Klembesch

X3.3/

Signal type

Function

Level

(Lenze setting: in bolt print)

A1

Digital
outputs

Ready for operation

0/+20 V at DC internal
0/+24 V at DC external

A2

Not prefabricated

7

GND, reference potential

A4

Frequency
output

DC−bus voltage

HIGH:
+18 V ... +24 V (HTL)
LOW: 0 V

59

DC supply for X3/A1 and X3/A2

+20 V (internal, bridge to
X3/20)

+24 V (external)

20

Internal DC voltage supply for control of
digital inputs and outputs

+20 V

±

10 %

28

Digital
inputs

Controller inhibit (CINH)

1 = START

E1

1)

Activation of JOG frequencies
JOG1 = 20 Hz
JOG2 = 30 Hz
JOG3 = 40 Hz

E1

E2

JOG1

1

0

E2

1)

JOG2

0

1

JOG3

1

1

E3

DC−injection brake (DCB)

1 = DCB

E4

Change of direction of rotation
CW/CCW rotation

E4

CW

0

CCW

1

E5

Not prefabricated

E6

Not prefabricated

1)

Optional frequency input 0 ... 102.4 kHz (single−tracked or double−tracked), configuration via C0425