5

Commissioning

Commissioning using Lenze settings

EDK82ZAFAC−001 DE/EN/FR 5.0

40

l

−H2−INB_01

Commissioning using Lenze settings

Step

Procedure

Comments

1.

Switch on the mains
voltage.

After approx. 1 second, the controller is ready for operation.
Controller inhibit is active.
Controller reaction
The green LED is blinking.
Keypad:

dc

(if attached)

2.

Control digital inputs.

Lenze setting

l

CW rotation:
– E1, E2, E3, E4: LOW

l

CCW rotation:
– E1, E2, E3: LOW
– E4: HIGH

Individual setting
Adapt digital inputs under C0007 or C0410.
The digital inputs must be controlled so that the drive can
start via terminal after controller enable.

3.

Select setpoint

Lenze setting
Setpoint: 0 ... +10 V
Individual setting

l

Depending on jumper position at module
– Apply master current to X3.1/1I or X3.1/2I or
– apply master voltage to X3.1/1U or X3.1/2U

l

Check C0034

4.

Enable controller via
terminal.

Lenze setting
X3.3/28 = HIGH (+12 V ... +30 V)
Controller reaction
The green LED is on.
Keypad:

c

Off

5.

The drive should be running now.

)

Note!

ƒ

The controller is only ready for operation if a HIGH signal is applied to
X3.3/28 (controller enable via terminal).
– Please observe that the controller can be inhibited through various

sources. All sources act like a series connection of switches.

– If the drive does not start although the controller has been enabled via

X3.3/28, check whether the controller has been inhibited through a
different source. Another source could be the

s−key of the keypad.

Advertising