Commissioning
Jumper positions for inputs
EDK82ZAFAC−001 DE/EN/FR 5.0
38
l
H1inbet−Jmpausgg
Jumper positions for inputs
10
9
8
7
2
1
4
3
6
5
Lenze setting (bold printing in tables)
1 − 3
2 − 4
7 − 9
8 − 10
)
Note!
If a setpoint potentiometer is supplied internally via X3.2/9, the jumper must
be set between 0 ... +5 V. Otherwise it is not possible to use the whole speed
range.
Analog inputs
Possible levels
0 ... +5 V
0 ... +10 V
−10 ... +10 V
X3.1/1U
Analog input 1, AIN1
Jumper
7 − 9: free
7 − 9
7 − 9
Code
C0034/1 = 0
C0034/1 = 0
C0034/1 = 1
X3.1/2U
Analog input 2, AIN2
Jumper
8 − 10: free
8 − 10
8 − 10
Code
C0034/2 = 0
C0034/2 = 0
C0034/2 = 1
Analog inputs
Possible levels
0 ... +20 mA
+4 ... +20 mA
+4 ... +20 mA
1)
X3.1/1I
Analog input 1, AIN1
Jumper
optional
optional
optional
Code
C0034/1 = 2
C0034/1 = 3
C0034/1 = 4
X3.1/2I
Analog input 2, AIN2
Jumper
optional
optional
optional
Code
C0034/2 = 2
C0034/2 = 3
C0034/2 = 4
1)
open−circuit monitored