Electrical installation

Mounting steps

4

EDK82ZM113−001 DE/EN/FR 1.1

39

l

H1_E_INST−Verdraht_EE2ZM−001

Mounting steps

2

1

0

3

E82ZM−005

How to connect the interference suppression module:
1. De−energise the control cabinet and fuse it against re−energisation.
2. Wait for at least 3 minutes before checking the standard device for isolation from

supply.

3. Connect the connecting cable of the motor interference suppression module

0 to the

terminals of the standard device (U, V, W, and PE).
– Observe the documentation of the standard device!

4. Apply the motor cable.

– Apply the motor cable to the terminals U’, V’, W’

1 and to the PE screw 2,

respectively.

– Apply the motor cable shielding extensively to the shield connection on the right

hand side and fix it using the shield clamp

3(included in the scope of supply).