Connection data, Technical data – Lenze E82ZAFBC001 User Manual

Page 31

Advertising
background image

Technical data

Connection data

2

EDK82ZAFBC−001 DE/EN/FR 7.2

31

l

H1_Daten−AlleMaßeInMM

Connection data

X3/

62

Resolution: 10 bit
Linearity error: ±0.5 %
Temperature error: 0.3 % (0 … +60 °C)
Carrying capacity I

max

= 2 mA

8

Resolution: 10 bit
Linearity error: ±0.5 %
Temperature error: 0.3 % (0 … +60 °C)
Input resistance

l

R

input

> 50 k

W

(voltage signal)

l

R

input

= 250

W

(current signal)

9

Carrying capacity I

max

= 10 mA

7

Electrically isolated to terminal X3/39 (GND2)

20

Carrying capacity:

S

I

max

= 40 mA

28

Input resistance: 3.3 k

W

1 = HIGH (+12 … +30 V), PLC level, HTL
0 = LOW (0 … +3 V), PLC level, HTL

E1

1)

E2

1)

E3

E4

39

Electrically isolated to terminal X3/7 (GND1)

A1

Carrying capacity:
I

max

= 10 mA, for internal supply

I

max

= 50 mA, for external supply

1)

Alternatively frequency input 0 … 10 kHz single−tracked or 0 ... 1 kHz double−tracked, configuration
via C0425

Advertising